Facility maintenance checklist

A facility maintenance checklist lists what a building needs checked, cleaned, or serviced each day, week, month, quarter, and year, and who does it. Copy the free version below for a school or small office. Contractor work is marked [L].

It comes from the team behind SherpaDesk, a helpdesk and PSA (professional services automation) tool a small IT team can run alone.

What Is A Facility Maintenance Checklist?

A facility maintenance checklist is a master schedule: one list per building, copied out for each round, from boilers and drains to exit signs. A building maintenance checklist is usually sorted one of two ways.

- By interval. Daily, weekly, monthly, quarterly, twice-yearly, and annual lists. - By system. HVAC, plumbing, electrical, life safety, grounds, and custodial, for teams that split work by trade.

Ours is sorted by interval, because a weekly walk is easier to finish than a trade list. Treat it as the preventive maintenance checklist for the whole building; equipment manuals cover single units.

Why Routine Building Care Matters

GAO estimates that 19 percent of districts canceled school in 2024-25 because of a facilities issue. Plumbing emergencies and extreme classroom temperatures were among the top reasons. GAO also found that districts with limited capacity for preventive maintenance had more chronic facility problems.

EPA adds the cost side: deferring system maintenance usually raises overall costs. A building maintenance checklist for a small office is shorter, but a leak under its sink ruins the same ceiling tile.

Copy The Facility Maintenance Checklist

Copy the block or download the same text. Keep one master per building, copy a section for each round, and record date, initials, result, and work order number on each line.

Facility maintenance checklist · plain text
FACILITY MAINTENANCE CHECKLIST
School or small office, daily to annual. This is the master
schedule: copy a section for each round.

Building:                         Year:
Checklist owner:                  Phone:
Fire marshal (AHJ) contact:
Approved room temperature range:

[L] = licensed or certified contractor (check your state's rules)
[*] = code-set item: confirm with the responsible authority
Mark [x] when checked; record date, initials, pass/fail, WO #.
Every problem found becomes its own work order.
Escalate safety failures immediately; record interim protection.

DAILY (opening and closing walk)
[ ] Exit routes and exits clear; exit signs lit [*]
[ ] Floors dry: no spills, loose tiles, or trip hazards
[ ] Restrooms cleaned and stocked; trash out; no leaks
[ ] Rooms within the approved range; no HVAC control alarms
[ ] Exterior doors latch; exits open from inside without a key;
    building secured at close
[ ] Walkways, parking lot, playground: clear of debris and ice;
    damage reported
[ ] Stairs: handrails firm, treads sound; burned-out lights
    in halls, stairs, and restrooms reported

WEEKLY
[ ] Faucets, flush valves, and sensors work; no slow drains
[ ] Ceilings, walls, and under sinks: no new water stains
[ ] Mechanical rooms: no leaks, unusual noise, odors, or storage
[ ] Electrical rooms: space in front of panels clear [*]
[ ] Network closet: cool, dry, locked, nothing stored
[ ] Supply and return vents unobstructed
[ ] Grounds: mow, trim, empty outdoor bins (in season)
[ ] Roof drains and gutters seen from the ground: clear

MONTHLY
[ ] Fire extinguishers: in place, gauge in range, tag initialed [*]
[ ] Emergency lights: 30-second activation test per your
    approved test procedure; log [*]
[ ] HVAC filters: check; replace per the manufacturer
[ ] First-aid and spill kits stocked; chemicals labeled and stored
[ ] Door closers, panic bars, and hinges work; doors latch
[ ] Water heaters: no leaks; checked per your operating procedure
[ ] Kitchens, storage, crawl spaces: no signs of pests
[ ] Open work orders older than 30 days reviewed

QUARTERLY
[ ] HVAC units: inspect and service per the unit procedure [L]
[ ] Boilers and furnaces: service per the manufacturer [L]
[ ] Inspect roof membrane, flashing, drains, rooftop units;
    record defects. From safe access or by your roofer
[ ] Exterior: walls, windows, sealant sound; no new foundation cracks
[ ] Parking lot and sidewalks: no new cracks/potholes; lights work

TWICE A YEAR
[ ] Schools under AHERA: visually check identified or assumed
    asbestos material per the management plan, at least every
    6 months; log date, name, condition changes; send to the
    designated person [*]
[ ] Season change: heating or cooling start-up [L]
[ ] Exposed pipes and irrigation: freeze protection, start or stop

ANNUAL
[ ] Fire extinguishers: annual maintenance, date recorded [L] [*]
[ ] Battery emergency lights: 90-minute power test, log [*]
[ ] Sprinklers: main drain flow test [L] [*]
[ ] This list reviewed: new equipment added, retired removed,
    contractor contacts updated

LONGER CYCLES (last done / next due)
[ ] Sprinklers: inspector's test valve, every 2 years [L] [*]
[ ] Schools: asbestos reinspection, every 3 years (AHERA) [L] [*]

ASK YOUR AHJ, INSURER, OR WATER PROVIDER, THEN ADD THE DATES
[ ] Testable backflow assemblies: test on your water provider's
    schedule [L] [*]
[ ] Electrical panels and switchgear: inspection or infrared scan [L]
[ ] Fire alarm panel and devices (NFPA 72), trained technician [L] [*]
[ ] Kitchen hood and grease duct cleaning [L]
[ ] Emergency generator testing [L]
[ ] Elevator inspection [L]
Facility maintenance checklist Plain text · 3.6 KB · daily to annual, contractor items marked · updated Nov 13, 2026
Download Checklist

Where The Life-Safety Intervals Come From

The [*] lines of the maintenance checklist follow rules you can look up; the table names each source.

Code-set items in the checklist (rules as of November 2026)
ItemIn the listWhat the rule says
Fire extinguishersMonthly look; annual maintenanceOSHA: visual inspection monthly, a maintenance check annually, record kept one year after the last entry, or the life of the shell if shorter
Emergency lights30-second test monthly; 90-minute battery test yearlySeattle Fire Department, for example: 30-second activation test monthly; 90-minute power test yearly for battery units; records kept 3 years
SprinklersMain drain yearly; test valve every 2 yearsOSHA, for systems that meet an OSHA rule: main drain flow test annually; inspector's test valve at least every two years
Automatic fire detectionAsk your AHJOSHA-required automatic detection systems: tested as often as needed, by a trained person
Backflow assembliesYour water provider's scheduleCalifornia, for example: field tested at least annually by certified testers
Asbestos (schools)At least every 6 months; reinspection every 3 yearsAHERA, for known or assumed asbestos material: surveillance at least every 6 months; reinspection every three years
Electrical roomsWeekly lookOSHA: panel working space may not be used for storage

Three daily lines rest on OSHA rules too. Exit routes must be free and unobstructed, and exit doors must open from the inside without keys, tools, or special knowledge. Walking surfaces must be kept free of hazards such as spills, leaks, snow, and ice.

Your fire marshal or fire code official, the authority having jurisdiction (AHJ), enforces the adopted fire code. Confirm fire-safety dates there, asbestos dates with the AHERA designated person, and backflow dates with your water provider. Texas, for example, requires a licensed tester to check a new irrigation backflow assembly.

OSHA sets its rules for employers; public schools are covered where the state runs an OSHA-approved State Plan. As one school facilities manager put it, "A lot of this will be dictated by the rules with your Authority having jurisdiction."

The [L] marks are cautious: they say who should usually do the work, and your state decides who may. OSHA, for one, lets only qualified persons work on electrical parts that haven't been deenergized.

For HVAC service intervals in a school, our guide to school facilities maintenance software walks through EPA's sample timeline.

How To Fill It In For Your Building

Work down the maintenance checklist once using the building plan and equipment manuals.

  1. Fill in the header

    Write the building, year, owner, fire marshal contact, and approved temperature range. One owner chases the overdue lines.

  2. Assign tasks to your team or landlord

    Remove absent equipment. For landlord responsibilities, record the contact and service dates.

  3. Name the equipment

    Give each unit an ID and a room: "RTU-2, roof above Room 12". Tag it the way you tag laptops; our school asset management software guide covers tags and audits.

  4. Write in the contractor for every [L] line

    Add the company, the phone number, and the date they're booked.

Example: One Month At A Middle School

Say you run Building B at Cedar Hill Middle School. Here is the monthly section of the maintenance checklist after the October walk.

Filled-in example · monthly section
MONTHLY · Cedar Hill Middle School, Building B · October 2026
[x] Fire extinguishers: in place, gauge in range, tag initialed
    10/06 R.M. Fail: Room B-114 gauge low. Spare placed. WO 3307.
[x] Emergency lights: 30-second activation test; log
    10/06 R.M. Fail: gym unit dark. Gym use paused pending
    safety review. WO 3308.
    10/14 R.M. Retest after repair: pass. Gym reopened.
[x] HVAC filters: check; replace per the manufacturer
    10/08 J.T. Pass. Two AHU-1 filters replaced.
[x] First-aid and spill kits stocked; chemicals labeled and stored
    10/08 J.T. Pass.
[x] Door closers, panic bars, and hinges work; doors latch
    10/09 R.M. Pass.
[x] Water heaters: no leaks; checked per your operating procedure
    10/09 J.T. Pass.
[x] Kitchens, storage, crawl spaces: no signs of pests
    10/10 R.M. Pass.
[x] Open work orders older than 30 days reviewed
    10/10 J.T. Two open; WO 3291 waiting on a part.

Each failure got its own work order and an interim step: a spare extinguisher that morning, and the gym paused until the light passed its retest. The inspection was complete; repair work stayed open until verified.

How To Keep A Maintenance Checklist Running

A school maintenance checklist fails quietly: the October walk happens, the November walk slips, and nobody notices until the fire marshal does. Three habits keep it alive.

Put each interval on a calendar, not in a binder

Calendar each interval per building. Our helpdesk automation guide explains scheduled tickets for weekly and monthly checks.

Keep the proof with the record

Keep the date, initials, and contractor's report with the check. Under AHERA, the surveillance record goes to the school's designated person for the management plan.

Review the maintenance checklist once a year

After the fire marshal's visit, add what the inspector flagged and drop what you retired. Schools can line the annual items up with the summer device refresh in our IT support for schools guide.

Subscribe to the SherpaDesk Blog.
Get Tips for Running IT With a Small Team.

Loading form…

Run The Checklist In SherpaDesk

How this works in SherpaDesk

Weekly and monthly lists become scheduled work orders

You set up a recurring ticket under Tickets > Scheduled with its days, time, and recurrence type, then attach a To Do template. Scheduled maintenance then creates and assigns each ticket with its task list.

Link the boiler or the sprinkler riser as an asset, and its location, work history, and service costs stay on one record. Locations synced from Microsoft 365 can carry sub-locations such as "Building 123/Room12". Printed tickets can carry a signature block for the contractor's sign-off.

A helpdesk and PSA a small IT team can run alone. No implementation project. No dedicated admin. K-12 pricing is by student enrollment; ask sales for a quote.

Office teams can compare per-agent plans on the pricing page.

See SherpaDesk Ticketing

Who this isn't for

This checklist covers routine checks for schools and offices run on walks, contractors, and work orders. For a regulated plant maintenance program, evaluate dedicated CMMS tools against the workflows you must follow.

Frequently Asked Questions

What does building maintenance include?

A building maintenance checklist covers six areas: HVAC, plumbing, electrical, life safety, grounds, and custodial work. Life safety means exits, extinguishers, emergency lights, sprinklers, and alarms. Schools under AHERA with known or assumed asbestos material add surveillance at least every 6 months. The checklist covers all six by interval.

What preventive measures should a manager perform to keep a facility properly maintained?

Write the schedule down, give each line one owner, and book contractors for the licensed work. Record every check with a date and initials, and open a work order for each problem. Review the list after each fire marshal inspection.

What is preventive maintenance of equipment?

Preventive maintenance is work done on a schedule before equipment fails: replacing an air filter, cleaning a coil, testing a battery. The opposite is reactive work after a breakdown, such as a boiler serviced only once a classroom goes cold. EPA notes that deferring it usually raises overall costs.

Which facility maintenance tasks need a licensed contractor?

We mark [L] on work a licensed or certified contractor usually does. That includes backflow tests, sprinkler and fire alarm tests, annual extinguisher service, asbestos reinspection, electrical panel work, and HVAC and boiler service. California, for example, requires certified backflow testers. Your state decides who may do each job.

How often should fire extinguishers be inspected?

OSHA requires a visual inspection every month and a maintenance check every year. The annual date is recorded and kept a year after the last entry, or the life of the shell if shorter. Stored-pressure dry chemical extinguishers that need a 12-year hydrostatic test are also emptied and maintained every 6 years.

About the author
Patrick Clements Co-founder & CEO, SherpaDesk

Patrick co-founded SherpaDesk and has led it as CEO since 2013. He has worked with IT service providers since 1998, first on network projects for schools and government offices, then on the helpdesk software their technicians use every day.

Published Nov 15, 2026 by

Run a help desk your clients can set their watch by